ООО "ПРОМЫШЛЕННАЯ АВТОМАТИЗАЦИЯ"
поставляет промышленное оборудование и электронные компоненты для автоматизации технологических процессов, зданий и сооружений, машиностроительных комплексов.

 

BK9055 | Ethernet TCP/IP Bus Couplers

 

The “Compact” BK9055 Bus Coupler connects EtherNet/IP with the modular, extendable electronic terminal blocks. One unit consists of one Bus Coupler, any number from 1 to 64 terminals (255 with K-bus extension) and one end terminal.

The Bus Coupler recognises the terminals to which it is connected, and performs the assignment of the inputs and outputs to the words of the process image automatically. The BK9055 Bus Coupler supports 10 Mbit/s and 100 Mbit/s Ethernet. Connection is through normal RJ 45 connectors. The IP address is set on the DIP switch (offset to a freely selectable start address). In networks with DHCP (a service for the allocation of the logical IP address to the physical node address [MAC-ID]) the Bus Coupler obtains its IP address from the DHCP server.

Ethernet/IP is the Industrial Ethernet standard of ODVA (Open DeviceNet Vendor Association). Ethernet/IP is based on Ethernet TCP/IP and UDP/IP – IP stands for Industrial Protocol. Essentially, the CIP (Common Industrial Protocol) used in ControlNet and DeviceNet was ported to Ethernet TCP/IP and UDP/IP.

Complex signal processing for analog I/Os, position measurement, …

The BK9000 and BK9050 Bus Couplers support the operation of all Bus Terminal types.

The analog and multi-functional Bus Terminals can be adapted to each specific application using the KS2000 configuration set. Depending on the type, the analog Bus Terminals' registers contain temperature ranges, gain values and linearisation characteristics. With the KS2000, the required parameters can be set on a PC. The Bus Terminals store settings permanently and in a fail-safe manner.

Optionally, the Bus Terminals can also be controlled by the control system. Via function blocks (FBs), the programmable logic controller (PLC) or the Industrial PC (IPC) handles configuration of the complete periphery during the start-up phase. If required, the controller can upload the decentrally created configuration data in order to centrally manage and store this data. Therefore, new adjustments are not necessary in the event of replacement of a Bus Terminal. The controller carries out the desired setting automatically after switching on.

 

System data 
Number of I/O stations only limited by IP addresses
Number of I/O points depending on controller
Data transfer medium 4 x 2 twisted pair copper cable; category 3 (10 Mbaud), category 5 (100 Mbaud)
Distance between stations 100 m between hub/switch and Bus Coupler
Data transfer rates 10/100 Mbaud
Topology star wiring

 

 

Technical data 
Number of Bus Terminals 64 (255 with K-bus extension)
Max. number of bytes fieldbus 512 byte input and 512 byte output
Digital peripheral signals 1,020 inputs/outputs
Analog peripheral signals 128 inputs/outputs
Protocol EtherNet/IP
Configuration possibility via KS2000
Data transfer rates 10/100 Mbaud, automatic recognition of the transmission rate
Bus interface 1 x RJ 45
Power supply 24 V DC (-15 %/+20 %)
Input current 320 mA max.
Starting current 2.5 x continuous current
Recommended fuse ≤ 10 A
Current supply K-bus 1,000 mA
Power contacts 24 V DC max./10 A max.
Electrical isolation 500 V (power contact/supply voltage/fieldbus)
Weight approx. 100 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE, UL

 

 

Accessories 
KS2000 configuration software for extended parameterisation
Cordsets cordsets and connectors
FC90xx-00xx PC Fieldbus Cards with PCI interface

 

 

Ordering information 
BK9055 EtherNet/IP “Compact” Bus Coupler for up to 64 Bus Terminals (255 with K-bus extension)
CX8095 EtherNet/IP Embedded PC

 

  Яндекс.Метрика