EL3314-0010 | 4-channel thermocouple input terminal, high-precision, with open-circuit recognition

The EL3314-0010 analog input terminal allows four thermocouples to be connected directly. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal high-precision temperature measurement at the terminal. The EL3314-0010 can also be used for mV measurement.

Technical data EL3314-0010
Number of inputs 4
Power supply via the E-bus
Thermocouple sensor types types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Distributed clocks
Input filter limit frequency typ. 1 kHz; dependent on sensor length, conversion time, sensor type
Connection method 2-wire
Wiring fail indication yes
Conversion time approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Voltage measurement ±78 mV (error: ±25 µV)
Temperature range in the range defined in each case for the sensor (default setting: type K; -200…+1,370 °C); voltage measurement: ±78 mV in 10 nV resolution
Resolution 24 bits, presentation adjustable: 0.1/0.01/0.001 °C per digit or 10 nV per digit
Measuring error @ 50 Hz filter, @ 25 °C ambient temperature:
type B: ±5.0 °C
type E: ±1.8 °C
type J: ±1.8 °C
type K: ±1.8 °C
type L: ±1.8 °C
type N: ±2.5 °C
type R: ±4.0 °C
type S: ±4.0 °C
type T: ±1.8 °C
type U: ±1.8 °C
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bus typ. 200 mA
Special features open-circuit recognition
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable