ООО "ПРОМЫШЛЕННАЯ АВТОМАТИЗАЦИЯ"
поставляет промышленное оборудование и электронные компоненты для автоматизации технологических процессов, зданий и сооружений, машиностроительных комплексов.

 

EP1809-, EP1819-002x | 16-channel digital input 24 V DC

 

The EP1809 and EP1819 EtherCAT Box modules with digital inputs acquire the binary control signals from the process level and transmit them, in an electrically isolated form, to the controller. The state of the signals is indicated by light emitting diodes. The signals are optionally connected via M8 (EP1809-0021) or M12 (EP1809-0022, EP1819-0022) screw type connectors. These versions are distinguished by input filters of different speeds.

The sensors are supplied from the box supply voltage US. The auxiliary voltage UP is not used in the input module, but may be connected in order to be relayed downstream.

 

Technical data EP1809-0021 EP1809-0022 EP1819-0021 EP1819-0022
Specification EN 61131-2, type 1/3
Number of inputs 16
Input connections M8, screw type M12, screw type M8, screw type M12, screw type
Protocol EtherCAT
Bus interface 2 x M8 socket, shielded, screw type
Nominal input voltage 24 V DC (-15 %/+20 %)
Input filter 3.0 ms 10 µs
“0“ signal voltage -3…+5 V (EN 61131-2, type 3)
“1“ signal voltage 11…30 V (EN 61131-2, type 3)
Input current typ. 3 mA (EN 61131-2, type 3)
Distributed clocks
Sensor supply derived from control voltage, max. 0.5 A total, short-circuit-proof
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 16 inputs
Current consumption from US (without sensor current) 130 mA
Electrical isolation 500 V
Weight approx. 250 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable

 

  Яндекс.Метрика