The KL4424 and KL4428 analog output terminals generate signals in the range between 4 to 20 mA. The power is supplied to the process level with a resolution of 12 bits and is electrically isolated. The output stage is powered by the 24 V supply. In the KL4424 Bus Terminal, the four outputs are 2-wire versions. The KL4428 variant combines eight channels in one housing and is particularly suitable for space-saving installation in control cabinets. The use of single conductor connection technology enables the connection of multi-channel actuator technology with minimum space requirements.
The Bus Terminals have a common ground potential. The power contacts are connected through. The reference ground of the outputs is the 0 V power contact. The LEDs indicate the data exchange with the Bus Coupler.
Technical data | KL4424 | KS4424 | KL4428 | KS4428 |
---|---|---|
Technology | single-ended | |
Number of outputs | 4 | 8 |
Power supply | 24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515) | |
Signal current | 4…20 mA | |
Load | 350 (short-circuit-proof) | 150 (short-circuit-proof) |
Output error | ±0. % (relative to end value) | ±0. % (relative to end value) |
Resolution | 12 bits | |
Conversion time | ~ 4 ms | ~ 8 ms |
Electrical isolation | 500 V (K-bus/signal voltage) | |
Current consumption power contacts | typ. 60 mA + load | |
Current consumpt. K-bus | typ. 20 mA | |
Bit width in the process image | output: 4 x 16 bit data (4 x 8 bit control/status optional) | output: 8 x 16 bit data (8 x 8 bit control/status optional) |
Special features | – | increased packing density |
Weight | approx. 75 g | |
Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
Relative humidity | 95 %, no condensation | |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
Protect. class/installation pos. | IP 20/variable | |
Pluggable wiring | for all KSxxxx Bus Terminals | |
Approvals | CE, UL, Ex, GL |