KL3051, KS3051, KL3052, KS3052 | 1-, 2-channel loop-powered input terminals 4…20 mA

The job of the KL3051 and KL3052 analog input terminals is to supply power to measuring transducers located in the field and to transmit analog measurement signals with electrical isolation to the automation device. The voltage for the sensors is supplied to the terminals via the power contacts. The power contacts can optionally be supplied with operating voltage in the standard way or via a power feed terminal (KL9xxx) with electrical isolation. The input electronics is independent of the supply voltage of the power contacts. The 0 V rail is the reference potential for the inputs. The run LEDs give an indication of the data exchange with the Bus Coupler. The error LEDs indicate an overload condition and a broken wire.


Technical data  
Number of inputs 1
Power supply 24 V DC via power contacts
Signal current 4…20 mA
Technology single-ended
Internal resistance 80 Ω + 0.7 V
Common-mode voltage UCM
Resolution 12 bits
Conversion time ~ 1 ms
Measuring error max ±0.3 % (relative to full scale value)
Surge voltage resistance 35 V max.
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts only load
Current consumpt. K-bus typ. 65 mA
Bit width in the process image input: 1 x 16 bit data (1 x 8 bit control/status optional)
Configuration no address or configuration setting
Special features with sensor supply
Weight approx. 70 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals CE, UL, Ex, GL



Special terminals  
KL3052-0010 Siemens S5 format
KL3052-0011 fast µP, scan time approx. 0.5 ms
KL3052-0012 changed diagnostic level ( 21.5 mA)
KL3052-0050 Siemens S7 format