For the KL1804 and KL1814 Bus Terminals, the reference ground for all inputs is the 0 V power contact. The versions have input filters with different speeds. The wires can be connected without tools in the case of solid wires using a direct plug-in technique.
The HD Bus Terminals (High Density) with increased packing density feature 16 connection points in the housing of a 12 mm terminal block.
Technical data | KL1804 | KL1814 |
---|---|---|
Connection technology | 3-wire | |
Specification | EN 61131-2, type 1/3 | |
Number of inputs | 4 | |
Nominal voltage | 24 V DC (-15 %/+20 %) | |
“0“ signal voltage | -3…+5 V (EN 61131-2, type 1/3) | |
“1“ signal voltage | 11…30 V (EN 61131-2, type 3) | |
Input filter | typ. 3.0 ms | typ. 0.2 ms |
Input current | typ. 3 mA (EN 61131-2, type 3) | |
Current consumpt. K-bus | typ. 10 mA | |
Current consumption power contacts | typ. 1 mA + load | |
Electrical isolation | 500 V (K-bus/field potential) | |
Bit width in the process image | 4 inputs | |
Configuration | no address or configuration setting | |
Conductor types | solid wire, stranded wire and ferrule | |
Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver | |
Rated cross-section | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² | |
Weight | approx. 60 g | |
Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
Relative humidity | 95 %, no condensation | |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
Protect. class/installation pos. | IP 20/variable (see documentation) | |
Approvals | CE, UL, Ex |