Technical data | KL1501 | KS1501 |
---|---|
Number of inputs | 2 |
Number of counters | 1 or 2 |
Nominal voltage | 24 V DC (-15 %/+20 %) |
“0“ signal voltage | -3…+5 V |
“1“ signal voltage | 15…30 V |
Counting frequency | max. 100 kHz (2 kHz for switching between up and down) |
Counter depth | 32 bits |
Input current | typ. 5 mA |
Max. output current | 0.5 A typ. (short-circuit-proof) per channel |
Current consumpt. K-bus | typ. 50 mA |
Electrical isolation | 500 V (K-bus/field potential) |
Bit width in the process image | 40 inputs/outputs: 32 bit data, 8 bit control/status |
Configuration | no address setting, configuration via Bus Coupler or controller |
Special features | 2 additional outputs |
Weight | approx. 50 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals | CE, UL, Ex |
Special terminals | |
---|---|
KL1501-0010 | gate-counter with auto-reset and setting A0 |
KL1501-0011 | up/down counter with 5 V inputs, 24 V DC outputs |